Configuration via software
(with optional LCC100 software)
An easy and friendly configuration with the software !
You can configure your own intermediary ranges.
Example : for a transmitter with a range of 0-1000 Pa, the minimum configurable range is 0-100 Pa.
For example, you can configure your transmitter with a range of -20 to +80 Pa, from 0 to +600 Pa,
or from -450 to +450 Pa...
• To access the configuration via software :
- Set the DIP switches as shown beside. Nota : the on-off switch 1 of the DIP switch 1 can be in
any position (selection of the analogic output 0-10 V or 4-20 mA).
- Connect the cable to the transmitter plug (see “connections”).
• Please refer to the user manual of the LCC 100 to make the configuration.
Please avoid any aggressive solvent.
Please protect the transmitter and its probes from any cleaning product
containing formol, that may be used for cleaning roots or ducts
Installation : mount the ABS plate on the wall (this plate is supplied with the
transmitter). Drilling : Ø 6 mm (with the screws and pins supplied with the
transmitter). Insert the transmitter on the plate (see A on the drawing beside)
and rotate its housing in clockwise direction until you hear a “click", which
confirms that the transmitter is correctly installed.
! Caution !
Once the transmitter is installed and
powered up, please make an autozero to
guarantee the correct working of the
transmitter in any position.
For a pressure transmitter, the minimum configurable range is 10% of the full range.
! Caution !